Back to Assets
Compliant
- Type
- 06 - Fire Detection Systems - Panels
- Tier
- ASSET
- Location
- Back of Main Shed
- Barcode
- —
- Make
- Notifier
- Model
- 2800
- Size
- 1 Loop
- Quantity
- —
- Expected life (yrs)
- —
- Installed
- —
- Base date
- —
- Last inspected
- 16 May 2025
- Inspection ref
- —
- Serviced by
- Scott Osborne
- Signed off
- —
- Active
- Yes
- Inspection order
- 0
Internal note
Battery Capacity Test Results 22/9/2023 Q = 0.62 Amp A = 4.32 Amp Required = 24.0 A/H Fitted = 2 x 12 volt 35 A/H Last Replaced = 22/06/2022 Result = PASS